What does Indoor CO2 and the Cross Draught conclude, in numbers, about “Bernoulli's Orifice and the Cross Draught: Wind Pressure, Stack Pressure and Openings in Series”?
Answer: Chapter 4 uses Bernoulli's orifice formula to show that a cross draught of 694 cubic metres per hour is driven by only 1.92 pascals.
Scope of the numbers: Marked boxes separate published evidence, runnable Python calculations (21 programs), classical sources and the author's hypotheses.
Data table
The numbers below are printed verbatim by the chapter's Python program and can be reproduced by running it. standard-library Python onlyprinted values that match the answer: 1.92, 694
| equal openings A1 = A2; Q in m^3/h and air changes per hour | |
| A each m2 U | 1 m/s U=2 m/s U=3 m/s U=5 m/s |
| 0.10 | 139 1.7 278 3.3 417 5.0 694 8.3 |
| 0.25 | 347 4.1 694 8.3 1042 12.4 1736 20.7 |
| 0.50 | 694 8.3 1389 16.5 2083 24.8 3472 41.3 |
| 1.00 | 1389 16.5 2778 33.1 4167 49.6 6944 82.7 |
| dP at 2 m/s across the building | 1.92 Pa |
| A1 1.0 m2 with A2 0.25 m2 at 2 m/s | 953 m^3/h |
| gain over 0.25 + 0.25 m2 | 1.372 times |
Show the full program
# Chapter 4. p41: wind-driven cross ventilation through two openings.
# Model: Bernoulli orifice flow Q = Cd A sqrt(2 dP / rho). Wind gives
# dP = 0.5 rho U^2 dCp across the building, so for two openings in series
# Q = Cd A_eff U sqrt(dCp), with 1/A_eff^2 = 1/A1^2 + 1/A2^2.
# Cd 0.61 (sharp-edged orifice), dCp 0.8 (windward +0.5, leeward -0.3)
# and the room of p21 (84 m^3) are illustrative textbook values.
# 风压驱动的穿堂风:两个开口串联的伯努利孔口流;系数为示意教科书值。
import math
RHO = 1.2
CD = 0.61
DCP = 0.8
V = 84.0
def a_eff(a1, a2):
return 1.0 / math.sqrt(1.0 / a1 ** 2 + 1.0 / a2 ** 2)
def q_wind(a1, a2, u, dcp=DCP, cd=CD):
dp = 0.5 * RHO * u * u * dcp
return cd * a_eff(a1, a2) * math.sqrt(2.0 * dp / RHO)
if __name__ == "__main__":
print("equal openings A1 = A2; Q in m^3/h and air changes per hour")
print("A each m2 U=1 m/s U=2 m/s U=3 m/s U=5 m/s")
for a in (0.1, 0.25, 0.5, 1.0):
cells = []
for u in (1.0, 2.0, 3.0, 5.0):
q = q_wind(a, a, u) * 3600
cells.append("{:6.0f} {:5.1f}".format(q, q / V))
print("{:8.2f} ".format(a) + " ".join(cells))
print("dP at 2 m/s across the building: {:.2f} Pa".format(
0.5 * RHO * 4 * DCP))
big = q_wind(1.0, 0.25, 2.0) * 3600
small = q_wind(0.25, 0.25, 2.0) * 3600
print("A1 1.0 m2 with A2 0.25 m2 at 2 m/s: {:.0f} m^3/h".format(big))
print("gain over 0.25 + 0.25 m2: {:.3f} times".format(big / small))Single source and citation
Fan, Y. (2026). Indoor CO2 and Cognitive Decline, Bernoulli Cross-Ventilation and an Engineering Re-reading of 'Storing Wind, Gathering Qi' (Version 1.0.0), Chapter 4: Bernoulli's Orifice and the Cross Draught: Wind Pressure, Stack Pressure and Openings in Series. 5D Library. DOI pending
DOI pending · monograph page goes live after publication · 5DL-B-194 · v1.0.0 · CC-BY-NC-ND-4.0
BibTeX
@book{fan2026194,
author = {Fan, Yafu},
title = {Indoor CO2 and Cognitive Decline, Bernoulli Cross-Ventilation and an Engineering Re-reading of 'Storing Wind, Gathering Qi'},
year = {2026},
publisher = {5D Library},
edition = {1.0.0},
note = {DOI pending}
}Other chapter answers in this book
- Chapter 1 · 1400 ppm in the Meeting Room: Three Controlled Exposure Experiments and Decision Scores
- Chapter 2 · The Stirred Tank: How an Eight-Person Meeting Room Climbs to 1400 ppm
- Chapter 3 · The Clean Air Delivery Rate of a Pot Plant: the Arithmetic of a Hundred Pots per Square Metre
- Chapter 5 · Pulse Ventilation and Dynamic Programming: a Window Schedule inside a Sawtooth
- Chapter 6 · A Concentration Is Not a Dose: Confounding, Rebreathed Air and Sensor Error
- Chapter 7 · Classical Sources East and West: Storing Wind and Gathering Qi in the Zangshu, and the Eight Winds of Vitruvius
- Chapter 8 · The Empirical Loop: Studio Ventilation Schedules, Reception-Room Closing Rates and a Plan for Refutation