What does Acoustics and the Psychology of Built Space conclude, in numbers, about “Carbon Dioxide, Ventilation and Decision-Making”?
Answer: Indoor CO~2~ is an indicator of ventilation, and 1,000 ppm is not a health limit. The well-mixed mass balance \(V\,dC/dt = NG - Q(C - C_{out})\) shows that six people in a 48.6 m³ room at one air change per hour pass 1,000 ppm in 18 minutes, and that a steady state below 800 ppm needs about 13 L/s of outdoor air per person. Satish and colleagues (2012) and Allen and colleagues (2016) reported marked falls in decision-test scores after injecting pure CO~2~ (about 945–2,500 ppm), but with small samples and calls for replication from the authors themselves; when Zhang and colleagues (2017) manipulated them separately, pure CO~2~ up to 3,000 ppm had no effect while bioeffluents did. The illustrative calculation shows that in field data CO~2~ and bioeffluents can hardly be separated. The next chapter returns to the ancients: how they wrote about wind, water, shadows and houses.
Scope of the numbers: This book is not medical advice; problems with hearing or sleep call for a doctor. Marked boxes separate published evidence, runnable Python calculations (15 programs, all checked), classical sources and the author's hypotheses.
Data table
The numbers below are printed verbatim by the chapter's Python program and can be reproduced by running it. standard-library Python onlyprinted values that match the answer: 1000, 13, 18, 48.6, 800
| room volume 48.6 m3; CO2 source 6 x 0.005 L/s | 108 L/h |
| ACH | outdoor air/person | steady state | at 60 min | minutes to 1000 | to 800 | |
| 0.5 | | 1.1 L/s | 4864 ppm | 2169 | 17 | 11 |
| 1.0 | | 2.2 L/s | 2642 ppm | 1825 | 18 | 11 |
| 2.0 | | 4.5 L/s | 1531 ppm | 1381 | 22 | 13 |
| 3.0 | | 6.8 L/s | 1161 ppm | 1124 | 31 | 14 |
| 4.0 | | 9.0 L/s | 976 ppm | 965 | never | 17 |
| 6.0 | | 13.5 L/s | 790 ppm | 789 | never | never |
| outdoor air needed to stay below 1000 ppm | 8.6 L/s per person |
| outdoor air needed to stay below 800 ppm | 13.2 L/s per person |
| G | 0.004 L/s each: minutes to 1000 ppm at ACH 0.5, 1, 2, 3 = 21, 24, 32, 77 |
Key formula
Show the full program
# Well-mixed room: V dC/dt = N G - Q (C - Cout). Six adults in a 4.5 x 4.0 x 2.7 m
# meeting room; G = 0.005 L/s per person (Persily & de Jonge 2017 tabulate about
# 0.0035-0.0056 L/s for seated adults at 1.2-1.4 met); outdoor 420 ppm; start at outdoor
# level. Q = ACH x V. Last line: the same room with G = 0.004 L/s (quiet sitting; Persily
# & de Jonge give about 0.0029-0.0039 L/s per adult at 1.0 met).
import math
V, N, G, C_OUT = 4.5 * 4.0 * 2.7, 6, 0.005e-3, 420.0 # m3, people, m3/s, ppm
SRC = N * G * 3600 * 1e6 # ppm x m3 per hour
def conc(ach, t_h, c0=C_OUT, src=SRC):
css = C_OUT + src / (ach * V)
return css - (css - c0) * math.exp(-ach * t_h), css
def minutes_to(ach, target, src=SRC):
css = conc(ach, 0, src=src)[1]
if css <= target:
return None
return -math.log((css - target) / (css - C_OUT)) / ach * 60
print(f"room volume {V:.1f} m3; CO2 source {N} x {G * 1e3:.3f} L/s"
f" = {N * G * 3.6e6:.0f} L/h")
print(" ACH | outdoor air/person | steady state | at 60 min | minutes to 1000 | to 800")
for ach in (0.5, 1, 2, 3, 4, 6):
q_pp = ach * V / 3.6 / N # L/s per person
c60, css = conc(ach, 1.0)
m1, m8 = minutes_to(ach, 1000), minutes_to(ach, 800)
f = lambda m: "never" if m is None else f"{m:5.0f}"
print(f" {ach:3.1f} | {q_pp:5.1f} L/s | {css:5.0f} ppm | {c60:5.0f} |"
f" {f(m1):>5s} | {f(m8):>5s}")
for target in (1000, 800):
print(f"outdoor air needed to stay below {target} ppm:"
f" {G * 1e3 / ((target - C_OUT) * 1e-6):.1f} L/s per person")
src4 = N * 0.004e-3 * 3600 * 1e6
print("G = 0.004 L/s each: minutes to 1000 ppm at ACH 0.5, 1, 2, 3 = "
+ ", ".join(f"{minutes_to(a, 1000, src4):.0f}" for a in (0.5, 1, 2, 3)))Single source and citation
Fan, Y. (2026). Architectural Acoustics, Reverberation Time and the Environmental Psychology of Built Space (Version 1.0.0), Chapter 6: Carbon Dioxide, Ventilation and Decision-Making. 5D Library. https://doi.org/10.5281/zenodo.23782090
DOI: 10.5281/zenodo.23782090 · Read the monograph · 5DL-B-031 · v1.0.0 · CC-BY-NC-ND-4.0
BibTeX
@book{fan2026031,
author = {Fan, Yafu},
title = {Architectural Acoustics, Reverberation Time and the Environmental Psychology of Built Space},
year = {2026},
publisher = {5D Library},
edition = {1.0.0},
doi = {10.5281/zenodo.23782090},
url = {https://doi.org/10.5281/zenodo.23782090}
}Other chapter answers in this book
- Chapter 1 · Sabine and Eyring: Reverberation Time and Speech Clarity
- Chapter 2 · Standing Waves, Room Modes and Low-Frequency Noise
- Chapter 3 · Open-Plan Offices and the Irrelevant Speech Effect
- Chapter 4 · Trees outside the Window: Fractal Dimension and Biophilic Design
- Chapter 5 · Illuminance, Spectrum and Ceiling Height
- Chapter 8 · Practice and a Pre-Registered Trial