关于「二氧化碳、通风与决策」,《建筑声学与空间环境心理学》给出的定量结论是什么?
结论:室内 CO~2~ 是通风的指示物,1,000 ppm 不是健康限值。充分混合的质量守恒方程 \(V\,dC/dt = NG - Q(C - C_{out})\) 给出:6 人在 48.6 立方米、每小时换气 1 次的会议室里,18 分钟就超过 1,000 ppm;稳态低于 800 ppm 需要每人约 13 升/秒新风。萨蒂什等人 2012 年与艾伦等人 2016 年报告了注入纯 CO~2~(约 945–2,500 ppm)后决策测验得分的明显下降,但样本小、作者呼吁重复;张等人 2017 年分开操纵后,纯 CO~2~ 到 3,000 ppm 没有影响,人体散发物有影响。示意计算显示,在现场数据中 CO~2~ 与人体散发物几乎无法分开。下一章回到古人:他们怎样谈论风、水、日影与房屋。
数据口径:本书不是医疗建议;听力、睡眠问题请就医。 书中以标注框区分已发表的证据、可运行的 Python 计算(15 段程序,全部核对)、原典与作者的假说。
对照数据表
下表数字由本章 Python 程序原样打印,可重新运行复现。 程序只用 Python 标准库与结论吻合的打印值: 1000, 13, 18, 48.6, 800
| room volume 48.6 m3; CO2 source 6 x 0.005 L/s | 108 L/h |
| ACH | outdoor air/person | steady state | at 60 min | minutes to 1000 | to 800 | |
| 0.5 | | 1.1 L/s | 4864 ppm | 2169 | 17 | 11 |
| 1.0 | | 2.2 L/s | 2642 ppm | 1825 | 18 | 11 |
| 2.0 | | 4.5 L/s | 1531 ppm | 1381 | 22 | 13 |
| 3.0 | | 6.8 L/s | 1161 ppm | 1124 | 31 | 14 |
| 4.0 | | 9.0 L/s | 976 ppm | 965 | never | 17 |
| 6.0 | | 13.5 L/s | 790 ppm | 789 | never | never |
| outdoor air needed to stay below 1000 ppm | 8.6 L/s per person |
| outdoor air needed to stay below 800 ppm | 13.2 L/s per person |
| G | 0.004 L/s each: minutes to 1000 ppm at ACH 0.5, 1, 2, 3 = 21, 24, 32, 77 |
核心公式
\[V\frac{dC}{dt} = NG - Q\,(C - C_{out}).\]
查看完整验算程序
# Well-mixed room: V dC/dt = N G - Q (C - Cout). Six adults in a 4.5 x 4.0 x 2.7 m
# meeting room; G = 0.005 L/s per person (Persily & de Jonge 2017 tabulate about
# 0.0035-0.0056 L/s for seated adults at 1.2-1.4 met); outdoor 420 ppm; start at outdoor
# level. Q = ACH x V. Last line: the same room with G = 0.004 L/s (quiet sitting; Persily
# & de Jonge give about 0.0029-0.0039 L/s per adult at 1.0 met).
import math
V, N, G, C_OUT = 4.5 * 4.0 * 2.7, 6, 0.005e-3, 420.0 # m3, people, m3/s, ppm
SRC = N * G * 3600 * 1e6 # ppm x m3 per hour
def conc(ach, t_h, c0=C_OUT, src=SRC):
css = C_OUT + src / (ach * V)
return css - (css - c0) * math.exp(-ach * t_h), css
def minutes_to(ach, target, src=SRC):
css = conc(ach, 0, src=src)[1]
if css <= target:
return None
return -math.log((css - target) / (css - C_OUT)) / ach * 60
print(f"room volume {V:.1f} m3; CO2 source {N} x {G * 1e3:.3f} L/s"
f" = {N * G * 3.6e6:.0f} L/h")
print(" ACH | outdoor air/person | steady state | at 60 min | minutes to 1000 | to 800")
for ach in (0.5, 1, 2, 3, 4, 6):
q_pp = ach * V / 3.6 / N # L/s per person
c60, css = conc(ach, 1.0)
m1, m8 = minutes_to(ach, 1000), minutes_to(ach, 800)
f = lambda m: "never" if m is None else f"{m:5.0f}"
print(f" {ach:3.1f} | {q_pp:5.1f} L/s | {css:5.0f} ppm | {c60:5.0f} |"
f" {f(m1):>5s} | {f(m8):>5s}")
for target in (1000, 800):
print(f"outdoor air needed to stay below {target} ppm:"
f" {G * 1e3 / ((target - C_OUT) * 1e-6):.1f} L/s per person")
src4 = N * 0.004e-3 * 3600 * 1e6
print("G = 0.004 L/s each: minutes to 1000 ppm at ACH 0.5, 1, 2, 3 = "
+ ", ".join(f"{minutes_to(a, 1000, src4):.0f}" for a in (0.5, 1, 2, 3)))唯一数据源与引用
范雅福(Fan, Y.). (2026). 《建筑声学、混响时间与空间环境心理学的物理模型》第 6 章「二氧化碳、通风与决策」(版本 1.0.0). 5D Library. https://doi.org/10.5281/zenodo.23782090
DOI: 10.5281/zenodo.23782090 · 阅读本章所在专著 · 5DL-B-031 · v1.0.0 · CC-BY-NC-ND-4.0
BibTeX
@book{fan2026031,
author = {Fan, Yafu},
title = {Architectural Acoustics, Reverberation Time and the Environmental Psychology of Built Space},
year = {2026},
publisher = {5D Library},
edition = {1.0.0},
doi = {10.5281/zenodo.23782090},
url = {https://doi.org/10.5281/zenodo.23782090}
}